KCC115E - KCC116EA - KCC116EB
Short Circuit and Over Current VATOR Guard
O/C VATOR and definite time S/C trip delays maintain discrimination
between parallelled generators. The fail-safe relay R3 (O/C & S/C)
should be used to open the generator breaker. R1 (O/C) and R2 (S/C) can
be used for local indication, alarm system or PM-System etc. All relays
latch after trip.
KCC115E2 - KCC116E2A - KCC116E2B
Short Circuit and Over Current
VATOR Guard
O/C VATOR and definite time S/C trip delays. R2 (O/C)
and the fail-safe relay R1 (S/C) should be used to open the generator
breaker. The common alarm relay R3 (S/C & O/C) can be used for local
indication, alarm system or PM-System etc. All relays latch after trip.
KCC115F - KCC116FA - KCC116FB
Short Circuit and Over Current Guard
Replaces the classic KCC115. Definite time O/C and S/C
trip delays. Fail-safe S/C relay. All relays latch after trip. Either
R1 (O/C) and R2 (S/C) can be used to trip generator breaker with R3 as a
common alarm or R3 can trip the generator breaker with R1/R2 used for
local indication, PMS or alarm system input etc.
KCC115F2 - KCC116F2A - KCC116F2B
Short Circuit and Over Current
Guard
Definite time O/C and S/C trip delays. Either R1 (O/C)
and R2 (S/C) can be used to trip generator breaker with R3 as a common
alarm or R3 can trip the generator breaker with R1/R2 used for
local indication, PMS or alarm system input etc. NON fail- safe latching
relays. Since all relays are NON fail-safe this version is only
suitable as a replacement for older installations.
KCC115G - KCC116GA - KCC116GB
Short Circuit and Over Current Guard
For marine emergency/harbour generator sets.
Definite time O/C and S/C trip delays. Non-latching O/C trip relay (R1)
and non-failsafe S/C trip relay (R2). If an engine is set as an
emergency generator only R2 (S/C) shall be used to open the generator
breaker as per the requirements of classification societies. In harbour
operation both relay R1 and R2 shall open the breaker. R3 operates on
both S/C and O/C and can be used for alarm system input etc.
KCC115H - KCC116HA - KCC116HB
Short Circuit and 2-level Over
Current Predictor Guard
2-level O/C settings. Definite time O/C and S/C trip
delays. Instead of the VATOR function the H-versions have 2 over current
set trip levels to reduce trip time in high over load situations.
"Predictor" early action on relays R1 and R2, both relays will trip
after full set O/C or S/C time. R3 is delayed and will trip after full set O/C time + 1sec or
S/C time + 200mS. R3 is used to open the generator breaker. R1 or R2
are used for bus-tie breaker opening or for preference load tripping.
KCC115H4 - KCC116H4A - KCC116H4B
Short Circuit and 2-level Over
Current Guard
2-level O/C settings. Definite time O/C and S/C trip
delays. Instead of the VATOR function the H-versions have two over
current set trip levels to reduce trip time in high over load
situations. All relays will trip after full set time. Individual alarm
relay outputs give flexibility for a variety of applications.
KCC115H5 - KCC116H5A - KCC116H5B
Short Circuit and 2-level Over
Current Predictor Guard
2-level O/C settings. Definite time O/C trip delays. "Predictor" early
action on R1 and R2, both relays will trip after full set O/C or S/C time. R3 is delayed and will trip after full set O/C time + 1sec or
S/C time + 200mS. R3 is used to open the breaker. R1 and R2 are used
for bus-tie breaker opening or for preference load tripping.
KCC115P - KCC116PA - KCC116PB
Short Circuit, VATOR Over Current and
Predictor Guard
The best choice for diesel electric systems to prevent totally black
out. VATOR O/C trip delay. Fail safe and latching R3. "Predictor" early
action on relays R1 and R2, R1 will trip after full set O/C and R2 after
full set S/C time. R3 is delayed and will trip after full set O/C time +
1sec or S/C time + 200mS. R3 is used to open the generator
breaker. R1 and/or R2 are used for bus tie breaker opening, preference
load tripping, PMS or alarm system input etc.
KCC115P2 - KCC116P2A - KCC116P2B
Short Circuit and Over Current
Predictor Guard
Definite time O/C and S/C trip delays. Fail safe and latching R3.
"Predictor" early action on relays R1 and R2, R1 will trip after full
set O/C and R2 after full set S/C time. R3 is delayed and will trip
after full set O/C time + 1sec or S/C time + 200mS. R3 is used to
open the generator breaker. R1 and/or R2 are used for bus tie breaker
opening, preference load tripping, PMS or alarm system input etc.
KCC115P3 - KCC116P3A - KCC116P3B
Short Circuit and Over Current
Predictor Guard (S/C only)
Definite time O/C and S/C trip delays. Fail safe and latching R3.
"Predictor" early action on relay R1 and R2, both relays will trip after
full set S/C time. R3 is delayed and will trip after full set O/C time +
1sec or S/C time + 200mS. R3 is used to open the generator
breaker. R1 and R2 are used for bus tie breaker opening, preference load
tripping, PMS or alarm system input etc.