MC17 is designed for use with the MXG105 system when generators are synchronised with the mains.
The MC17 sets a load level to maintain either a fixed import or fixed export level.
The unit produces a 0-5mA output which can be connected directly into the load sharing input of an MCE105D controller (terminals 29,30) which is equivalent to 0-100% of the generator rating.