The digitally controlled KCM161xQx is designed to monitor the insulation level between a non-grounded (IT) AC mains and its protective earth in systems with frequency converters . The unit is for land, marine and offshore use.
An AC or DC auxiliary voltage is required for the unit, if powered from a separate source the network can also be monitored during inactive (standby) conditions. Only ONE KCM161xQx can be connected to each IT-system. The ohmmeter and the triple-zone status LEDs give at a glance the clear safety message:
IDV MEASURING PRINCIPLE
Insulation is measured between the complete galvanically interconnected AC network and its protective earth.
The unit injects a DC measuring signal into the monitored system. The signal flows to ground via the path of the insulation fault, the level of flow indicates the insulation resistance. The measuring accuracy is not influenced by any normal kind of load attached to the AC network.
This unit is used for any land, marine or offshore installations. Start of monitoring function is delayed when auxiliary power is switched on (default 10 secs delay). The unit has minimum of 9 seconds detection time for any insulation fault.
Trip levels and delays are settable on unit rear. A trip LED flashes when the trip level is passed, the relay trips when the delay has elapsed. The timer resets if the fault is removed during countdown.
MEGGER SAFE
When auxiliary power is
OFF the unit input is automatically protected against "megger" test voltages up to 1.4kVDC, and incorrect measurements caused by the unit’s input impedance are avoided.
OUTPUTS
The KCM161FQx has an isolated
analogue output proportional to meter reading. If output is used for remote meter reading, we recommend 0-1mA for the slave indicator.
SAFETY
When a voltage adapter (CHx) is used the signal to terminals 4 and 6 on KCM161xQx is limited to a safe level, avoiding any dangerous voltage exposure to personnel.
The KCM161xQx range is designed to comply with specification IMCA D 045 "Code of Practice for the Safe Use of Electricity Under Water" issued by IMCA.
The unit meets IEC60092-504 and the relevant environmental and EMC tests specified in IEC60068/60092 and IEC61000/60533 respectively, to comply with the requirements of the major Classification Societies.
HIGH VOLTAGE ADAPTOR
Voltage Adaptor CH163-1,4 is used for Insulation Guard KCM161xQx when the monitored line voltage is higher than 690VAC.
INTELLIGENT SETTING ASSISTANCE
KCM161xQx has a built-in Assistance tool for setting/verification of the trip levels and the analogue output.
When either the Warning or Alarm potmeter on the front is operated
by user, the slave meter goes into Assistance Mode and meter reading and
analogue output will reflect the potmeter setting.
Reset / Parallelling Disable Function
KCM161xQx has a built-in disable function (available only when DC Aux.
Supply is applied). When connecting two or more IT-networks together
only one unit can be active, the other(s) must be disabled. When unit is
disabled the power led will flash every 2 seconds to indicate that unit
is inactive.
KCM161EQ & KCM161FQ - KCM161EQG & KCM161FQG
Scale range: 0-1000kΩ - ∞ (>6MΩ)
This unit is used for industrial, marine and offshore installations with frequency converters. Start of monitoring function is delayed when auxiliary power is switched on (default 5 secs delay).
The unit has a detection time of 6-9 seconds for any insulation fault.
Direct connection up to 690V line voltage.
Up to 1,4kV via
HV adaptor CH163x