KCM26x Series
 
KCM26x - AC INSULATION GUARD WITH MEASURING LOOP SUPERVISION
  • Direct connection up to 690V line voltage, up to 6,6kV with HV adapter for both single or three phase systems
  • Continuous supervision of measuring loop continuity
  • 2-level insulation relays and loop continuity relay
  • Immune to earth capacitance and voltage surges
  • For use in land, marine, offshore, sub-sea and ocean floor installations
  • Complies with IMCA D 045 Code of Practice
  • Analogue output proportional to meter reading (F-version)
  • Optional slave indicator
Application
The prime purpose of the digitally controlled KCM26x is basically identical to the "traditional" KCM16x Insulation Guard range. An auxiliary Measuring Input Loop Continuity Monitoring Facility has been added to notify the operator if a measuring loop disruption may cause the meter to read a too high insulation level.

An AC or DC auxiliary voltage is required for the unit, if powered from a separate source the network can also be monitored during standby conditions.

The unit has C/O relay outputs for Warning, Alarm and loop failure. The Alarm relay is fail to safety configured. A trip LED flashes when the trip level is passed, the relay trips when the delay has elapsed. The timer resets if the fault is removed during countdown.

Only ONE KCM26x can be connected to each IT-system. The ohmmeter and the triple-zone status LEDs give at a glance the clear safety message:
  • ALARM
  • WARNING
  • HEALTHY
General
IDV MEASURING PRINCIPLE
Insulation is measured between the complete galvanically interconnected AC network and its protective earth. The signal flows to ground via the path of the insulation fault, the level of flow indicates the insulation resistance. The measuring accuracy is not influenced by any normal kind of load attached to the AC network, the processing time for KCM26x is approximately 400mS.

MEASURING LOOP ALARM
A sensing resistor is mounted at the furthest end of the monitored loop in a separate Loop Resistance Sensor Module (LRSM-1,4 or LRSM-5). There are no restrictions on distance from the sensing resistor to the KPM26x unit. There is a fixed delay of 60 seconds on the loop failure alarm.

The Loop alarm will notify the operator by activating LED LOOP FAILURE and trip relay 3. A disruption in the input measuring loop may cause the guard to falsely read a too high insulation level. The Measuring Input Loop Continuity Monitoring Facility is of special importance during lasting standby conditions (motors, lanterns etc).
 
MEGGER SAFE
When auxiliary power is OFF the unit input is automatically protected against "megger" test voltages up to 1.4kVDC, and incorrect measurements caused by the unit’s input impedance is avoided.

OUTPUTS
All F versions have an isolated analogue output proportional to meter reading. If output is used for remote meter reading, we recommend 0-1mA for the slave indicator.

SAFETY
When a voltage adapter (CHx) is used the signal to terminals 4 and 6 on KCM261x and KCM263x is limited to a safe level, avoiding any dangerous voltage exposure to personnel.

The unit meets IEC60092-504 and the relevant environmental and EMC tests specified in IEC60068/60092 and IEC61000/60533 respectively, to comply with the requirements of the major Classification Societies.

INTELLIGENT SETTING ASSISTANCE
KCM26x has a built-in Assistance tool for setting/verification of the trip levels and the analogue output.

When either the Warning or Alarm potmeter on the rear is operated by user, the meter goes into Assistance Mode and meter reading and analogue output will reflect the potmeter setting.

Reset / Parallelling Disable Function
KCM26x has a built-in disable function (available only when DC Aux. Supply is applied). When connecting two or more IT-networks together only one unit can be active, the other(s) must be disabled. When unit is disabled the power led will flash every 2 seconds to indicate that unit is inactive.

KCM261E & KCM261F - KCM261G & KCM261GF
Scale range: 0-1000kΩ - ∞ (>6MΩ)

This unit is used for marine, ROV and offshore installations. Start of monitoring function is delayed when auxiliary power is switched on (default 5 secs delay).

Direct connection up to 690V line voltage.
Up to 1,4kV via HV adaptor CH163x

NB! Loop Resistance Sensor Module LRSM-x must be used together with all KCM26x models.
Loop Resistance Sensor Module for KC26x series

KCM263E & KCM263F - KCM263G & KCM263GF
Scale range: 0-10MΩ - ∞ (>60MΩ)

This unit is used for marine, ROV and offshore installations. Start of monitoring function is delayed when auxiliary power is switched on (default 10 secs delay).

Direct connection up to 690V line voltage.
Up to 6,6kV via HV adaptor CH163x or AN6,6 series.

NB! Loop Resistance Sensor Module LRSM-x must be used together with all KCM26x models.
Loop Resistance Sensor Module for KC26x series


KCM263E2 & KCM263F2 - KCM263G2 & KCM263GF2
Scale range: 0-10MΩ - ∞ (>60MΩ)

This unit is used for hospital, industrial, marine and offshore installations. Start of monitoring function is delayed when auxiliary power is switched on (default 10 secs delay).

Direct connection up to 690V line voltage.
Up to 6,6kV via HV adaptor CH163x or AN6,6 series.

NB! Loop Resistance Sensor Module LRSM-x must be used together with all KCM26x models.