Insulation is measured between the complete galvanically
interconnected AC network and its protective earth.
The unit injects a
sequentially coded measuring signal into the monitored system. The
signal flows to ground via the path of the insulation fault, the level
of flow indicates the insulation resistance. The measuring accuracy is
not influenced by any normal kind of load attached to the AC network.
Trip levels and delays are settable on unit front. A trip LED flashes
when the trip level is passed, the relay trips when the delay has
elapsed. The timer resets if the fault is removed during countdown.
MEGGER SAFE
All
F versions have an isolated
analogue output proportional to
insulation level. If output is used for remote meter reading, we
recommend 0-1mA for the slave indicator.
SAFETY
When a voltage adapter (ARx or ANx) is used the signal to
terminals 4 and 6 on KCM165x is limited to a safe level,
avoiding any dangerous voltage exposure to personnel.
The KCM165x range is designed to comply with specification IMCA D 045
"Code of Practice for the Safe Use of Electricity Under Water" issued by
IMCA.
The unit meets IEC60092-504 and the relevant environmental and EMC
tests specified in IEC60068/60092 and IEC61000/60533 respectively, to
comply with the requirements of the major Classification Societies.
INTELLIGENT SETTING ASSISTANCE
KCM165x has a built-in Assistance tool for setting/verification of the trip levels and the analogue output.
When either the Warning or Alarm potmeter on the front is operated
by user, the slave meter goes into Assistance Mode and meter reading and
analogue output will reflect the potmeter setting.
Reset / Parallelling Disable Function
KCM165x has a built-in disable function (available only when DC Aux.
Supply is applied). When connecting two or more IT-networks together
only one unit can be active, the other(s) must be disabled. When unit is
disabled the power led will flash every 2 seconds to indicate that unit
is inactive.